Hebrew

R-Com

Data delivery

R-Com

The R-COM is a general purpose GSM/GPRS RTU. The R-COM ensures that no matter where you are, crucial information will find its way straight to your cellphone in the form of SMS messages. Real-time information is sent to your device according to the specific settings of your R-COM. When off-site, in addition to predefined setting information, you can ask your R-COM for information as well; simply send an SMS inquiry to get an immediate answer.

General

The R-COM provides 24/7 global communication coverage for automatic SMS alert messages, SMS I/O inquiries and SMS I/O settings. Versatile, reliable and quickly configured, the R-COM is a cost-effective, DIN rail mountable RTU, featuring up to 6 A/I, 8 D/I, 2 D/O and 1 EIA RS232 serial port.

RTU Configuration Software

All automatic settings are done by the CONFIGURATOR software. This easy-to-use RTU configuration software provides a user-friendly environment for setting the R-COM behavior. It supports both local and remote download/upload for easy PC-RTU data transformation.

Communication

R-COM uses the popular GSM/GPRS network to transmit and receive data. No need for expensive antennas, frequency licensing or a power-consuming radio transmitter. No need to deal with transmission interruptions or worry about distance limitations. Simply use the R-COM to get highly effective communication results, thus saving time and money.

PLC External Device

The R-COM can be used either as a standalone unit, or it can be connected to a PLC. When connected to a PLC, the R-COM controls the PLC I/Os and registers. It serves as a cellular gateway, enabling completely interactive mobile communication between you and your PLC. Adjustable, reliable and easy-to-use, the R-COM is a versatile PLC interfaced communication tool, supporting Modbus, Unitronics, Hostlink and many other serial communication protocols.

Settings

The R-COM provides both automatic-alert and user-interference services. CONFIGURATOR You are free to configure the automatic-alert behavior of the R-COM to meet your specific needs. The R-COM built-in user-interference system makes it possible to set/get registers and I/O values from the comfort of your mobile phone. You can simply send an SMS message to set the digital output value, turn it on/off, obtain I/O values, set the time and date, set/get register values and more.

Supervising, monitoring and tracking your system have never been easier; all of these can easily be done from the comfort of your cellphone. The R-COM gives you more freedom, removing worries about possible malfunction and providing you with real-time qualitative information.

Technical Specifications

HW interfaces

RS-232

One DB9 male (standard EIA)

Digital Inputs

8 (5-24VDC)

Analog Inputs

2 Current (0-20mA)
2 Voltage (0-10v)
2 Resistance (PT-100)

Digital Output

2 (Relay 5A)

Leds

4 yellow

Physical Characteristic

Dimension

105X63X90mm

Weight

240gr

Cover

Rigid plastic – Lexan 920

Assembly

Appropriate for mounting On DIN 35mm Rail

Power supply Specification

Power supply

12-24VDC

Maximum momentary power failure

10mS

Maximum power consumption

24 W  (1A)

Typical power consumption

While
transmit 1.8W
no transmit 1.1W

Current consumption at 12V Continues

90mA

Environment

Operating Temperature

-25C to 55C

Storage Temperature

-40C to 85C

Operating Humidity

5% to 95%
Non - condensing

Protocols

PLC protocols

MODBUS, Matusushita, Unitronics, Omron, IZUMI and others

Cellular Network Interface

Band

Quad-Band EGSM 850/900/1800/1900 MHz

Protocols

CSD, SMS, GPRS class 10, Mobile station class B

Internal modem

Telit 864

Modem Approvals

Fully type approved according to R&TTE
CE, GCF, FCC, PCTRB, IC

Technology

GSM network + SIM card

Voltage analog input Specification

Number of input

2

Resolution bit

10 bit   (10mV)

Conversion speed

10mS

Input voltage

0-10VDC

Precision

2% (20mV)

Input impedance

619KOhm (10%)

Offset/Gain

Offset value- 0 at 0VDC
GAIN value: 0-10V= 0-1024 / 65535

Current analog input Specification

Number of input

2

Resolution bit

10 bit   (0.02mA)

Conversion speed

10mS

Input voltage

0-20mA DC

Precision

2% (0.4mA)

Input impedance

200Ohm (10%)

Offset/Gain

Offset value- 0 at 0mA
GAIN value: 0-20mA=0-1024 / 65535

PT100 analog input Specification

Number of input

2

PT100 range

(-20) -  (80)

Isolation

None

Resolution bit

8 bit  (0.3 Celsius degree)

Conversion speed

10mS

Precision

Worst case 0.4 Celsius degree

Input impedance

20kohm

Connection options

Three (compensation) or two wires

DC input Specification

Number of input

8

Number of com

2

Input voltage

12-24VDC

Input current

5 mA  24 VDC

Off to on

>5.2V

On to off

<4.2V

Response time

10mS

Frequency maximum

50Hz

Minimum pulse width

80us

Isolation

Optocoupler

Output Specification

Number of output

2

Output type

Relay for 0-30 VAC/VDC

Max resistive load

5A 30 VDC

Contact life cycle

100,000 operations minimum (contact rating)

Minimum load

150W

Maximum inductive load

1250 VA

Response time

6mS

Isolation

By relay 1G ohm

 

 

 Print    Send to a friend
All Rights Resereved Copyright © 2008 - Remmon Ltd. Built By: EKDESIGN - Web Design